NetSight
critical10.0

CVE-2016-9343

An issue was discovered in Rockwell Automation Logix5000 Programmable Automation Controller FRN 16.00 through 21.00 (excluding all firmware versions prior to F…

Impact

An issue was discovered in Rockwell Automation Logix5000 Programmable Automation Controller FRN 16.00 through 21.00 (excluding all firmware versions prior to FRN 16.00, which are not affected). By sending malformed common industrial protocol (CIP) packet, an attacker may be able to overflow a stack-based buffer and execute code on the controller or initiate a nonrecoverable fault resulting in a denial of service.

Affected products

VendorProductAffected versions
RockwellautomationSoftlogix 5800 Controller Firmware
Versions 18.00, 19.00, 20.00, 21.00
RockwellautomationRslogix Emulate 5000 Firmware
Versions 18.00, 19.00, 20.00, 21.00
RockwellautomationGuardlogix 5570 Controller Firmware
Versions 16.00, 17.00, 18.00, 19.00, 20.00, 20.010
RockwellautomationFlexlogix L34 Controller Firmware
Version 16.00
RockwellautomationControllogix L55 Controller Firmware
Versions 16.00, 16.020, 16.022
RockwellautomationControllogix 5570 Redundant Controller Firmware
Versions 20.00, 20.050, 20.055, 21.00
RockwellautomationControllogix 5570 Controller Firmware
Versions 18.00, 19.00, 20.010, 20.013, 21.00
RockwellautomationControllogix 5560 Redundant Controller Firmware
Versions 16.00, 19.00, 20.00, 20.050, 20.055
RockwellautomationControllogix 5560 Controller Firmware
Versions 16.00, 16.020, 16.022, 17.00, 18.00, 19.00
Rockwellautomation1769 Compactlogix L3x Controller Firmware
Versions 16.00, 16.020, 16.023, 17.00, 18.00, 19.00
Rockwellautomation1769 Compactlogix L23x Controller Firmware
Versions 16.00, 17.00, 18.00, 19.00, 20.00, 20.010
Rockwellautomation1769 Compactlogix 5370 L3 Controller Firmware
Versions 20.00, 20.010, 20.013, 21.00

Weakness classification

References