NetSight
high7.5

CVE-2018-4840

A vulnerability has been identified in DIGSI 4 (All versions < V4.92), EN100 Ethernet module DNP3 variant (All versions < V1.05.00), EN100 Ethernet module IEC …

Impact

A vulnerability has been identified in DIGSI 4 (All versions < V4.92), EN100 Ethernet module DNP3 variant (All versions < V1.05.00), EN100 Ethernet module IEC 104 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.30), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). The device engineering mechanism allows an unauthenticated remote user to upload a modified device configuration overwriting access authorization passwords.

Affected products

VendorProductAffected versions
SiemensSiprotec Compact 7sj80 Firmware
before 4.77
SiemensSiprotec Compact 7sk80 Firmware
before 4.77
SiemensSiprotec 4 7sj66 Firmware
before 4.30
SiemensDigsi 4
before 4.92
SiemensEn100 Ethernet Module Iec 104 Firmware
All versions
SiemensEn100 Ethernet Module Dnp3 Firmware
All versions
SiemensEn100 Ethernet Module Modbus Tcp Firmware
All versions
SiemensEn100 Ethernet Module Profinet Io Firmware
All versions
SiemensEn100 Ethernet Module Iec 61850 Firmware
before 4.30

Weakness classification

References