NetSight
critical9.8

CVE-2022-33174

Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface.

Impact

Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.

Affected products

VendorProductAffected versions
PowertekpdusBasic Pdu Firmware
before 3.30.30
PowertekpdusPm Pdu Firmware
before 3.30.30
PowertekpdusPiml Pdu Firmware
before 3.30.30
PowertekpdusSmart Pim Firmware
before 3.30.30
PowertekpdusSmart Pos Firmware
before 3.30.30
PowertekpdusSmart Pom Firmware
before 3.30.30
PowertekpdusSmart Poms Firmware
before 3.30.30

Weakness classification