NetSight
critical9.8

CVE-2022-33175

Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 have an insecure permissions setting on the user.token field that is acc…

Impact

Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 have an insecure permissions setting on the user.token field that is accessible to everyone through the /cgi/get_param.cgi HTTP API. This leads to disclosing active session ids of currently logged-in administrators. The session id can then be reused to act as the administrator, allowing reading of the cleartext password, or reconfiguring the device.

Affected products

VendorProductAffected versions
PowertekpdusBasic Pdu Firmware
before 3.30.30
PowertekpdusPm Pdu Firmware
before 3.30.30
PowertekpdusPiml Pdu Firmware
before 3.30.30
PowertekpdusSmart Pim Firmware
before 3.30.30
PowertekpdusSmart Pos Firmware
before 3.30.30
PowertekpdusSmart Pom Firmware
before 3.30.30
PowertekpdusSmart Poms Firmware
before 3.30.30

Weakness classification

References