A vulnerability has been identified in Desigo PXM30-1 (All versions < V02.20.126.11-41), Desigo PXM30.E (All versions < V02.20.126.11-41), Desigo PXM40-1 (All …

Impact

A vulnerability has been identified in Desigo PXM30-1 (All versions < V02.20.126.11-41), Desigo PXM30.E (All versions < V02.20.126.11-41), Desigo PXM40-1 (All versions < V02.20.126.11-41), Desigo PXM40.E (All versions < V02.20.126.11-41), Desigo PXM50-1 (All versions < V02.20.126.11-41), Desigo PXM50.E (All versions < V02.20.126.11-41), PXG3.W100-1 (All versions < V02.20.126.11-37), PXG3.W100-2 (All versions < V02.20.126.11-41), PXG3.W200-1 (All versions < V02.20.126.11-37), PXG3.W200-2 (All versions < V02.20.126.11-41). The device embedded browser does not prevent interaction with alternative URI schemes when redirected to corresponding resources by web application code. By setting the homepage URI, the favorite URIs, or redirecting embedded browser users via JavaScript code to alternative scheme resources, a remote low privileged attacker can perform a range of attacks against the device, such as read arbitrary files on the filesystem, execute arbitrary JavaScript code in order to steal or manipulate the information on the screen, or trigger denial of service conditions.

Affected products

VendorProductAffected versions
SiemensDesigo Pxm30-1 Firmware
before 02.20.126.11-41
SiemensDesigo Pxm30.E Firmware
before 02.20.126.11-41
SiemensDesigo Pxm40-1 Firmware
before 02.20.126.11-41
SiemensDesigo Pxm40.E Firmware
before 02.20.126.11-41
SiemensDesigo Pxm50-1 Firmware
before 02.20.126.11-41
SiemensDesigo Pxm50.E Firmware
before 02.20.126.11-41
SiemensPxg3.W100-1 Firmware
before 02.20.126.11-37
SiemensPxg3.W100-2 Firmware
before 02.20.126.11-41
SiemensPxg3.W200-1 Firmware
before 02.20.126.11-37
SiemensPxg3.W200-2 Firmware
before 02.20.126.11-41