CVE-2022-40182
A vulnerability has been identified in Desigo PXM30-1 (All versions < V02.20.126.11-41), Desigo PXM30.E (All versions < V02.20.126.11-41), Desigo PXM40-1 (All …
Impact
A vulnerability has been identified in Desigo PXM30-1 (All versions < V02.20.126.11-41), Desigo PXM30.E (All versions < V02.20.126.11-41), Desigo PXM40-1 (All versions < V02.20.126.11-41), Desigo PXM40.E (All versions < V02.20.126.11-41), Desigo PXM50-1 (All versions < V02.20.126.11-41), Desigo PXM50.E (All versions < V02.20.126.11-41), PXG3.W100-1 (All versions < V02.20.126.11-37), PXG3.W100-2 (All versions < V02.20.126.11-41), PXG3.W200-1 (All versions < V02.20.126.11-37), PXG3.W200-2 (All versions < V02.20.126.11-41). The device embedded Chromium-based browser is launched as root with the “--no-sandbox” option. Attackers can add arbitrary JavaScript code inside “Operation” graphics and successfully exploit any number of publicly known vulnerabilities against the version of the embedded Chromium-based browser.
Affected products
| Vendor | Product | Affected versions |
|---|---|---|
| Siemens | Desigo Pxm30-1 Firmware | before 02.20.126.11-41 |
| Siemens | Desigo Pxm30.E Firmware | before 02.20.126.11-41 |
| Siemens | Desigo Pxm40-1 Firmware | before 02.20.126.11-41 |
| Siemens | Desigo Pxm40.E Firmware | before 02.20.126.11-41 |
| Siemens | Desigo Pxm50-1 Firmware | before 02.20.126.11-41 |
| Siemens | Desigo Pxm50.E Firmware | before 02.20.126.11-41 |
| Siemens | Pxg3.W100-1 Firmware | before 02.20.126.11-37 |
| Siemens | Pxg3.W100-2 Firmware | before 02.20.126.11-41 |
| Siemens | Pxg3.W200-1 Firmware | before 02.20.126.11-37 |
| Siemens | Pxg3.W200-2 Firmware | before 02.20.126.11-41 |