CVE-2023-36380
A vulnerability has been identified in CP-8031 MASTER MODULE (All versions < CPCI85 V05.11 (only with activated debug support)), CP-8050 MASTER MODULE (All ver…
Impact
A vulnerability has been identified in CP-8031 MASTER MODULE (All versions < CPCI85 V05.11 (only with activated debug support)), CP-8050 MASTER MODULE (All versions < CPCI85 V05.11 (only with activated debug support)). The affected devices contain a hard-coded ID in the SSH `authorized_keys` configuration file. An attacker with knowledge of the corresponding private key could login to the device via SSH. Only devices with activated debug support are affected.
Affected products
| Vendor | Product | Affected versions |
|---|---|---|
| Siemens | Cp-8050 Firmware | before 05.11 |
| Siemens | Cp-8031 Firmware | before 05.11 |