NetSight
critical10.0

CVE-2026-3611

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration.

Impact

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

Affected products

VendorProductAffected versions
HoneywellIq4e Firmware
before 3.30
HoneywellIq412 Firmware
before 3.30
HoneywellIq422 Firmware
before 3.30
HoneywellIq4nc Firmware
before 3.30
HoneywellIq41x Firmware
before 3.30

Weakness classification

References