NetSight
kritisch9.8

CVE-2021-31884

A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All …

Auswirkung

A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.4), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.19), APOGEE PXC Modular (BACnet) (All versions < V3.5.4), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.19), Capital VSTAR (All versions with enabled Ethernet options), Desigo PXC00-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC00-U (All versions >= V2.3 and < V6.30.016), Desigo PXC001-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC100-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC12-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC128-U (All versions >= V2.3 and < V6.30.016), Desigo PXC200-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC36.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC50-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC64-U (All versions >= V2.3 and < V6.30.016), Desigo PXM20-E (All versions >= V2.3 and < V6.30.016), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus Source Code (All versions), TALON TC Compact (BACnet) (All versions < V3.5.4), TALON TC Modular (BACnet) (All versions < V3.5.4). The DHCP client application assumes that the data supplied with the “Hostname” DHCP option is NULL terminated. In cases when global hostname variable is not defined, this may lead to Out-of-bound reads, writes, and Denial-of-service conditions. (FSMD-2021-0014)

Ein Angreifer kann die Lücke über das Netzwerk ausnutzen, ohne Anmeldung, ohne Zutun eines Nutzers. Bei Erfolg: hohes Risiko, dass Daten ausgelesen werden, hohes Risiko, dass Daten oder Systeme verändert werden, hohes Risiko für Ausfälle.

Betroffene Produkte · Siemens

ProduktBetroffene Versionen
Apogee Modular Building Controller Firmware
Alle Versionen
Apogee Modular Equiment Controller Firmware
Alle Versionen
Apogee Pxc Compact Firmware
vor 2.8.19
vor 3.5.4
Apogee Pxc Modular Firmware
vor 2.8.19
vor 3.5.4
Capital Vstar
Alle Versionen
Desigo Pxc00-e.d Firmware
ab 2.3 vor 6.30.016
Desigo Pxc00-u Firmware
ab 2.3 vor 6.30.016
Nucleus Net
Alle Versionen
Nucleus Readystart V3
vor 2017.02.1
Nucleus Source Code
Alle Versionen
Talon Tc Compact Firmware
vor 3.5.4
Talon Tc Modular Firmware
vor 3.5.4

Schwachstellenklasse

Referenzen