CVE-2021-35533
Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500…
Auswirkung
Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).
Ein Angreifer kann die Lücke über das Netzwerk ausnutzen, ohne Anmeldung, ohne Zutun eines Nutzers. Bei Erfolg: hohes Risiko für Ausfälle.
Betroffene Produkte · Hitachienergy
| Produkt | Betroffene Versionen |
|---|---|
| Rtu500 Firmware | Versionen 12.0, 12.2, 12.4 |