NetSight
medium6.0

CVE-2026-127123

P-Net before 1.0.4 releases the Application Relationship of an RPC session, without the abort procedure, when a fragment of a request has another data represen…

Impact

P-Net before 1.0.4 releases the Application Relationship of an RPC session, without the abort procedure, when a fragment of a request has another data representation (endianness) than the first fragment of the call. The application is not told that the Application Relationship is gone, the cyclic data stops, and the resources of the Application Relationship are left referencing a cleared structure. Another host can then connect in its place. A host with ADJACENT network access that has observed the activity UUID of the connection, which is sent in clear in every RPC request, can do this with one PDU.

An attacker can exploit this from the same local network, without logging in, without any action by a user. Specific conditions have to be met, which makes an attack harder. If it succeeds: low risk of data or systems being changed, high risk of outages.

Affected products · RT-Labs

ProductAffected versions
P-Net
before 1.0.4

Weakness classification

References