NetSight
high7.5

CVE-2026-58114

A vulnerability has been identified in SIMATIC BATCH V9.1 (All versions), SIMATIC Information Server 2020 (All versions), SIMATIC Information Server 2022 (All …

Impact

A vulnerability has been identified in SIMATIC BATCH V9.1 (All versions), SIMATIC Information Server 2020 (All versions), SIMATIC Information Server 2022 (All versions), SIMATIC PCS 7 V9.1 (All versions), SIMATIC Process Historian 2020 (All versions), SIMATIC Process Historian 2022 (All versions), SIMATIC WinCC Runtime Professional V17 (All versions), SIMATIC WinCC Runtime Professional V18 (All versions), SIMATIC WinCC Runtime Professional V19 (All versions), SIMATIC WinCC Runtime Professional V20 (All versions), SIMATIC WinCC Runtime Professional V21 (All versions), SIMATIC WinCC V7.5 (All versions), SIMATIC WinCC V8.0 (All versions), SIMATIC WinCC V8.1 (All versions). Affected systems do not properly secure their remote user authentication with the deprecated NTLM protocol. This could allow unauthenticated remote attackers, who have achieved a machine in the middle position, to relay NTLM authentication and impersonate a legitimate user. The potential impact depends on the services that are accessible, e.g. a SQL server used by WinCC.

An attacker can exploit this over the network, without logging in, but a user has to do something, such as open a file or a link. Specific conditions have to be met, which makes an attack harder. If it succeeds: high risk of data being read, high risk of data or systems being changed, high risk of outages.

Affected products · Siemens

ProductAffected versions
SIMATIC BATCH V9.1
before *
SIMATIC Information Server 2020
before *
SIMATIC Information Server 2022
before *
SIMATIC PCS 7 V9.1
before *
SIMATIC Process Historian 2020
before *
SIMATIC Process Historian 2022
before *
SIMATIC WinCC Runtime Professional V17
before *
SIMATIC WinCC Runtime Professional V18
before *
SIMATIC WinCC Runtime Professional V19
before *
SIMATIC WinCC Runtime Professional V20
before *
SIMATIC WinCC Runtime Professional V21
before *
SIMATIC WinCC V7.5
before *
SIMATIC WinCC V8.0
before *
SIMATIC WinCC V8.1
before *

Weakness classification

References