CVE-2026-3611
The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration.
Auswirkung
The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
Ein Angreifer kann die Lücke über das Netzwerk ausnutzen, ohne Anmeldung, ohne Zutun eines Nutzers. Bei Erfolg: hohes Risiko, dass Daten ausgelesen werden, hohes Risiko, dass Daten oder Systeme verändert werden, hohes Risiko für Ausfälle. Der Angriff kann über die verwundbare Komponente hinaus wirken.
Betroffene Produkte · Honeywell
| Produkt | Betroffene Versionen |
|---|---|
| Iq412 Firmware | vor 3.30 |
| Iq41x Firmware | vor 3.30 |
| Iq422 Firmware | vor 3.30 |
| Iq4e Firmware | vor 3.30 |
| Iq4nc Firmware | vor 3.30 |