NetSight
kritisch10.0

CVE-2026-3611

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration.

Auswirkung

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

Ein Angreifer kann die Lücke über das Netzwerk ausnutzen, ohne Anmeldung, ohne Zutun eines Nutzers. Bei Erfolg: hohes Risiko, dass Daten ausgelesen werden, hohes Risiko, dass Daten oder Systeme verändert werden, hohes Risiko für Ausfälle. Der Angriff kann über die verwundbare Komponente hinaus wirken.

Betroffene Produkte · Honeywell

ProduktBetroffene Versionen
Iq412 Firmware
vor 3.30
Iq41x Firmware
vor 3.30
Iq422 Firmware
vor 3.30
Iq4e Firmware
vor 3.30
Iq4nc Firmware
vor 3.30

Schwachstellenklasse

Referenzen